You can see bite marks on cable jacket
Outer insulation is nicked, shredded, or missing on one or more cables in the crawlspace.
Start here: Shut off the affected circuit before getting close enough to inspect it.
Direct answer: If rats chewed wires in your crawlspace, assume the damaged cable is unsafe until proven otherwise. The right first move is to shut off the affected circuit or main power if you are not sure which circuit it is, then inspect only from a safe distance and plan on a licensed electrician for the repair.
Most likely: Most often, the real problem is exposed conductor damage on branch-circuit cable, sometimes with insulation packed around it from nesting. That can leave a dead circuit, nuisance tripping, arcing, or a hot spot you cannot see from the room above.
Rodent-chewed wiring is not a cosmetic issue. In the field, a lot of these calls look minor at first and then turn into multiple damaged spots once the insulation and nesting are moved back. Reality check: one visible chew mark often is not the only one. Common wrong move: patching the first damaged spot you see and missing a second one a few feet away.
Don’t start with: Do not start by taping over bite marks, splicing live wiring, or turning breakers back on just to see what happens.
Outer insulation is nicked, shredded, or missing on one or more cables in the crawlspace.
Start here: Shut off the affected circuit before getting close enough to inspect it.
Lights, outlets, or equipment on one side of the house lost power, often after hearing scratching or finding droppings.
Start here: Check for a tripped breaker or GFCI first, then leave the circuit off if it trips again.
A breaker will not stay on, or it trips shortly after reset.
Start here: Stop resetting it. That strongly suggests conductor damage or a short in the chewed run.
There is a hot plastic or burning smell, sometimes stronger near a crawlspace access or along a baseboard.
Start here: Turn off power immediately and treat it as an urgent electrical hazard.
This is the most common real failure. Even if copper is not fully exposed, damaged insulation can arc against framing, metal, or another conductor.
Quick check: With power off, look for tooth marks, flattened spots, or colored conductor insulation showing through the outer cable jacket.
Rats usually travel the same path and may chew more than one section, especially near nesting material or tight framing penetrations.
Quick check: Follow the cable visually as far as you safely can and look for repeated chew marks, droppings, or shredded insulation nearby.
If the breaker trips immediately or soon after reset, the chewed section may be contacting metal, damp material, or another conductor.
Quick check: Turn the breaker fully off, then on once. If it trips again, leave it off and stop testing.
Darkened insulation, a sharp burnt smell, or crackling means the damage is no longer just physical wear. It has become an active fire risk.
Quick check: From a safe distance, look for soot, melted jacket, or brittle blackened insulation and do not disturb it further.
This is a high-risk wiring problem. You want the area de-energized before anyone gets near damaged cable, damp soil, metal ducting, or plumbing.
Next move: You have made the area safer to inspect and reduced the chance of shock or arcing while you look around. If you cannot confidently de-energize the area, do not enter the crawlspace. Call an electrician.
What to conclude: The first job here is stabilization, not repair. Safe shutdown comes before diagnosis.
Sometimes homeowners find droppings and assume the wiring is damaged when the actual problem is just a tripped breaker or GFCI. Other times the breaker is tripping because the cable really is chewed. You want to sort that out early.
Next move: If power returns and stays on, you still need the crawlspace wiring inspected, but there may not be an active short at this moment. If the breaker trips again or a GFCI will not reset, stop. The damaged wiring likely needs repair before the circuit can be used safely.
What to conclude: A breaker or GFCI that will not hold is a strong sign the chew damage is affecting the conductors, not just the outer jacket.
You need enough information to judge urgency and scope, but this is not the time to start moving cables around. Chewed insulation can fall apart when touched.
Next move: You will know whether this looks like isolated jacket damage, multiple damaged sections, or active heat damage that needs urgent professional repair. If the view is blocked, the cable disappears into insulation, or the damage runs into a tight area you cannot see, do not start pulling things apart. Call an electrician.
Not every chewed cable is the same. Some can stay safely de-energized until repair. Others need same-day attention because the damage is already heating or affecting occupied areas.
Next move: You will have a clear next move: emergency electrician now, or scheduled electrician with the circuit left off. If you still are not sure how serious it is, err on the safe side and keep the circuit off until a licensed electrician inspects it.
Electrical repair alone is not enough if rats are still active. Otherwise the new work can get chewed again, sometimes within days.
A good result: You end up with a safe repaired circuit and a lower chance of repeat damage.
If not: If new damage appears or the breaker trips again after repair, the electrician needs to inspect for another damaged section or a separate affected circuit.
What to conclude: The job is not done when the lights come back on. It is done when the wiring is repaired and the rats are gone.
No. Tape is not a safe final repair for chewed branch-circuit cable. If the inner conductor insulation is damaged, the cable may need a proper splice in an accessible box or a replaced section, and that is electrician work in most homes.
That can still be unsafe. Sometimes the inner conductor insulation looks intact until the cable is moved or loaded. In a crawlspace, where access is poor and damage is often repeated, the safe call is to leave the circuit off and have it inspected.
The chewing may have let hot, neutral, or ground contact each other, metal, damp material, or framing. That creates a short or fault, and the breaker is doing its job by shutting the circuit down.
Yes if there is burning smell, smoke, soot, melted insulation, repeated tripping, or the damaged cable feeds critical equipment. If none of those are present, it may be a same-week repair, but the circuit should stay off until it is fixed.
Yes. If the rats are still active, the new wiring can get chewed again. Electrical repair and rodent exclusion need to happen together for the fix to last.