Nothing at the outdoor unit runs
No fan, no compressor sound, and no vibration at the outdoor unit when the thermostat is calling.
Start here: Start with thermostat mode and setpoint, then check the HVAC breakers and the outdoor disconnect.
Direct answer: If the heat pump compressor is not starting, the most common homeowner-level causes are no real call from the thermostat, a tripped breaker or disconnect, a badly restricted filter or coil causing a lockout, or an outdoor unit sitting in a defrost or fault condition. If the outdoor fan runs but the compressor stays silent or just hums, the problem is usually beyond safe DIY.
Most likely: Start by confirming the thermostat is actually calling, the indoor filter is not packed, and the outdoor unit has full power. Then separate three lookalikes: nothing outside runs, only the outdoor fan runs, or the unit is iced over.
A compressor that will not start can look like a dead heat pump, weak heat, or a system that blows room-temperature air. Reality check: many compressor complaints turn out to be a power, airflow, or control issue you can spot from the ground. Common wrong move: resetting breakers over and over when the outdoor unit is trying to tell you there is a real electrical or mechanical fault.
Don’t start with: Do not start by replacing the compressor, capacitor, contactor, or control parts. On a heat pump, those are high-risk guesses and often not homeowner-safe repairs.
No fan, no compressor sound, and no vibration at the outdoor unit when the thermostat is calling.
Start here: Start with thermostat mode and setpoint, then check the HVAC breakers and the outdoor disconnect.
You hear the fan outside, but there is no deeper compressor sound and the air indoors does not get properly warm or cool.
Start here: Check for icing, dirty filter, and obvious fault behavior, then stop before opening electrical compartments.
The outdoor unit makes a short hum, click, or brief start attempt, then quits.
Start here: Shut the system off and do not keep forcing restarts. That pattern needs a technician.
The house warms slowly, AUX or EM heat shows often, and the outdoor unit may run oddly or not at all.
Start here: Confirm the outdoor unit is powered and not iced over, then decide whether this is a compressor issue or an auxiliary-heat issue.
A schedule, wrong mode, dead batteries, or a small setpoint difference can leave the outdoor unit idle even though the system seems 'on.'
Quick check: Set the thermostat to the needed mode and move the setpoint at least 3 to 5 degrees past room temperature.
A tripped breaker, pulled disconnect, or partial power loss can leave the compressor off or the whole outdoor unit dead.
Quick check: Check for a tripped HVAC breaker and make sure the outdoor disconnect is fully seated and not switched off.
A packed filter, blocked coil, or heavy frost can make a heat pump stop normal compressor operation to protect itself.
Quick check: Inspect the indoor filter, return grilles, and the outdoor coil for dirt, snow, leaves, or solid ice.
If the fan runs but the compressor does not, or it hums and trips out, the trouble is often in the start circuit, controls, or the compressor itself.
Quick check: Listen for humming, clicking, or repeated short attempts, then stop at observation only.
A lot of no-compressor calls start with the thermostat not asking the outdoor unit to run long enough or in the right mode.
Next move: If the outdoor unit starts after a short delay and normal heating or cooling returns, the issue was likely settings, timing, or thermostat demand. If there is still no outdoor response, move on to power checks before assuming a bad compressor.
What to conclude: This separates a control-call problem from a true outdoor unit failure.
A heat pump compressor cannot start without full outdoor power, and this is one of the most common safe checks a homeowner can make.
Next move: If the unit starts and runs normally after power is restored, monitor it through a full cycle. If the breaker trips again, or the unit still will not start, stop resetting and continue with non-invasive checks only.
What to conclude: Repeated trips or partial operation point to an electrical fault, seized load, or another problem that is not fixed by more resets.
A heat pump that is starved for airflow or buried in frost can shut down compressor operation or perform so poorly that it looks like the compressor never came on.
Next move: If the unit restarts after thawing or after restoring airflow, and it now runs through a normal cycle, the shutdown was likely protective rather than a failed compressor. If the outdoor fan runs but the compressor still does not start, or icing returns quickly, the problem has moved past basic maintenance.
This is the key split. A completely dead outdoor unit often points to power or control loss. A running fan with no compressor points much more strongly to a pro-level fault.
Next move: If your observations clearly match one pattern, you can avoid random part swapping and make the next move cleaner. If the sounds and behavior are inconsistent, leave the system off and have it diagnosed under load by a technician.
Once the safe checks are done, the remaining likely causes involve live electrical testing, refrigerant diagnosis, or compressor condition. Those are not good guess-and-buy jobs.
A good result: A clean symptom report usually shortens diagnosis and helps avoid unnecessary parts.
If not: If the home cannot maintain safe indoor temperature, arrange prompt HVAC service rather than forcing more restarts.
What to conclude: At this point the likely fixes are in the outdoor electrical or refrigerant side, and that is where safe DIY ends on most heat pumps.
Repair Riot may earn a commission from qualifying purchases, at no extra cost to you.
That usually points to a problem beyond basic DIY, such as a compressor-start issue, an outdoor control fault, or a sealed-system problem. First rule out a dirty filter, heavy icing, and obvious power issues. If the fan keeps running without the compressor, stop there and schedule service.
Yes, indirectly. A badly restricted heat pump air filter can cause poor airflow, icing, or protective shutdown behavior that makes the compressor stop or perform erratically. It is one of the first things worth checking because it is safe, common, and cheap to fix.
No. Reset it once only. If it trips again, the system likely has a real electrical or mechanical fault. Repeated resets can overheat wiring and make the repair more expensive.
Not by itself. Light frost can be normal in heat mode, but heavy ice buildup is not. A dirty filter, blocked airflow, defrost problem, or refrigerant issue can all cause icing. If the unit is heavily iced and the compressor still will not start, shut it down and have it checked.
On a heat pump, that is usually not a good homeowner repair path unless you are trained and have already confirmed the fault safely. Those parts live in a high-voltage compartment, and guessing wrong is common. This page is better used to confirm when the problem has moved into pro service.