Nothing runs at all
Thermostat is on Cool, but you do not hear the indoor unit or the outdoor unit start.
Start here: Check thermostat mode, setpoint, batteries if used, and both HVAC breakers before anything else.
Direct answer: When the air conditioner inside unit is not running, the usual causes are a thermostat setting issue, a clogged filter causing a freeze-up or shutdown, a condensate safety switch stopping the system, or lost power to the indoor air handler. If the thermostat is calling for cooling but the indoor blower stays dead, the problem moves toward the air handler power supply, blower section, or controls.
Most likely: Start with the easy tells: thermostat set to Cool with the fan on Auto, a badly plugged air filter, water in the drain pan, and any tripped breaker or service switch near the indoor unit.
First separate whether the whole system is dead or just the indoor blower. If the outdoor unit runs but nothing moves inside, shut the system off and check for ice, a soaked drain pan, and indoor power loss before you go any deeper. Reality check: a lot of 'bad blower' calls turn out to be a wet float switch or a filter packed solid. Common wrong move: resetting breakers over and over without finding out why they tripped.
Don’t start with: Do not start by replacing the thermostat, blower motor, or control parts. On this symptom, a drain safety trip or simple power issue is more common than a failed major component.
Thermostat is on Cool, but you do not hear the indoor unit or the outdoor unit start.
Start here: Check thermostat mode, setpoint, batteries if used, and both HVAC breakers before anything else.
You hear the outside condenser, but there is little or no air from the vents and the inside unit is quiet.
Start here: Turn cooling off and look for a clogged filter, ice at the indoor coil area, or a condensate safety shutdown.
The air handler makes a short hum, buzz, or click, but the blower never gets up to speed.
Start here: Shut power off to the indoor unit and stop there if you are not comfortable around electrical compartments. This points more toward blower or control trouble.
The system was cooling, then stopped, and you find water in the pan, around the unit, or near the drain line.
Start here: Check for a full drain pan or tripped condensate float switch before chasing electrical parts.
A bumped mode, wrong fan setting, dead batteries, or a thermostat not actually calling for cooling can make the indoor unit look dead.
Quick check: Set the thermostat to Cool, lower the setpoint at least 3 to 5 degrees, and leave the fan on Auto first, then try Fan On to see whether the blower responds.
A packed filter can choke airflow, let the coil ice up, and leave you with little airflow or a blower that seems not to be running normally.
Quick check: Pull the air filter and inspect it in good light. If it is gray and matted over, replace it. Look for frost or ice at the indoor coil cabinet or refrigerant line.
Many systems shut the indoor unit down when the drain pan fills or the condensate line backs up, especially in humid weather.
Quick check: Look for water in the auxiliary pan, around the air handler, or at the drain outlet. A raised float or wet pan is a strong clue.
A tripped breaker, pulled service disconnect, or switched-off furnace or air handler service switch will stop the inside unit even if the thermostat is calling.
Quick check: Check the indoor HVAC breaker and the light-switch-style service switch mounted on or near the air handler or furnace.
A lot of no-run complaints start with a thermostat that is not really sending a cooling or fan call.
Next move: If the blower starts on Fan On or the system starts cooling normally, the issue was likely a setting problem, weak thermostat batteries, or a temporary control glitch. If the thermostat appears normal but the indoor unit stays silent, move to airflow, drain, and power checks.
What to conclude: You are confirming whether the problem is a simple control call issue or a real no-run condition at the indoor unit.
Restricted airflow is one of the most common reasons an AC stops moving air properly or shuts down after running awhile.
Next move: If a new filter and a full thaw restore normal airflow, the immediate problem was likely airflow restriction or freeze-up. If the filter was clean or the blower still will not run after thawing, keep going. The shutdown may be from condensate protection or indoor power loss.
What to conclude: A dirty filter is the easy fix. Ice points to an airflow or cooling problem, but you still need the indoor blower running before judging the rest of the system.
On many systems, a backed-up drain line or full pan will stop the indoor unit to prevent water damage.
Next move: If the indoor unit starts after the pan drains and the float resets, the shutdown was likely caused by a clogged condensate line or pan overflow. If the pan is dry and the float is not tripped, or the unit still does not run, check indoor power next.
The indoor unit can lose power even when the thermostat looks normal and the outdoor unit still tries to run.
Next move: If the indoor unit starts after a breaker reset, service switch correction, or properly seated panel, you found the immediate cause. If the breaker trips again, the blower only hums, or the unit stays dead with confirmed power available, stop DIY and schedule service.
At this point the safe homeowner fixes are usually done, and the remaining causes are more technical and higher risk.
A good result: If cooling returns and stays stable, your repair path was likely filter, drain, or power related.
If not: If the indoor unit still will not run after these checks, the remaining likely causes are inside the air handler and should be diagnosed by a pro.
What to conclude: You have ruled out the common homeowner-level causes and narrowed the call down to a much more useful service diagnosis.
Repair Riot may earn a commission from qualifying purchases, at no extra cost to you.
That usually points to an indoor-side problem such as a clogged filter and frozen coil, a condensate float switch shutdown, lost power to the air handler, or a blower section fault. Start with filter, drain pan, service switch, and breaker checks.
Yes. A badly clogged filter can choke airflow enough to freeze the indoor coil or make the system shut down abnormally. It is one of the first things worth checking because it is common and easy to fix.
Look for water in the drain pan, around the indoor unit, or at the drain line. If the pan is full and the float is raised, that is a strong sign the safety switch stopped the system to prevent overflow.
No. Reset it once only. If it trips again, leave the system off. Repeated breaker trips usually mean a motor, wiring, or control problem that needs proper diagnosis.
That is a different symptom path. Once the blower is running, move your diagnosis toward cooling performance rather than no-run causes. Check the warm-air or not-cooling symptom page instead of replacing indoor blower parts blindly.